This document is a user manual for NEO-DYN 100P, 101P, 110P, 142P, 180P, 200P, 201P adjustable pressure switches; 152P and 160P adjustable differential pressure switches
This manual covers the Neo-Dyn Enclosure 3X weatherproof electromechanical pressure switches, PN 610-0008 Rev C. Models 100P, 101P, 110P, 200P and 201P are gauge pressure switches, models 142P and 180P are vacuum switches, and models 152P and 160P are differential pressure switches. The units are intended for pneumatic and hydraulic systems up to 10,000 psig, have IP66 weatherproof enclosures that meet NEMA 3, 3R, 3S, 4, 4X and 13 requirements, and carry the CE Mark.
The manual explains mounting, process connections, process media, electrical connections and setpoint adjustment, followed by troubleshooting and complete specifications. Setpoints are adjusted with a nut inside the housing, except on models 101P and 201P, where the adjustment is external. Standard switches switch up to 15 amp at up to 250 VAC in single-pole configuration and up to 11 amp at up to 250 VAC in double-pole configuration.
| Weight | approximately 3 pounds (1.4 kg) each |
|---|---|
| Conduit connection | 1/2 - 14 NPT female |
| Standard pressure port, Model 142P | 1/2 - 14 NPT female |
| Ingress protection | IP66 |
| Enclosure types | NEMA 3, 3R, 3S, 4, 4X, 13 |
| Form C3X (SPDT) rating | 15 amp @ 125 or 250 VAC; 5 amp resistive @ 28 VDC |
| Form CC3X (DPDT) rating | 11 amp and 1/4 hp @ 125 or 250 VAC |
| Standard temperature rating | -40°C (-40°F) to +121°C (+250°F) |
| Maximum pressure, Model 200P18 | 10,000 psig (690 bar) operating, 15,000 psig (1034 bar) proof |
Models 100P, 101P, 110P, 142P, 180P, 200P and 201P, plus differential pressure switches 152P and 160P.
Setpoints are adjusted by turning an adjustment nut located inside the housing; on models 101P and 201P the adjustment is external.
The standard configuration switches up to 15 amp at up to 250 VAC single-pole, and up to 11 amp at up to 250 VAC double-pole.
The switches have weatherproof enclosures with IP66 ingress protection that meet NEMA 3, 3R, 3S, 4, 4X and 13 requirements.