This document is about the user manual of fem4x, fem4p, rem4x, fxm4x fan coils
This installation instruction covers FEM4X, FEM4P, REM4X and FXM4X fan coils. FEM4P models serve 1-1/2 to 4 ton systems, while FEM4X, FXM4X and REM4X models serve 1-1/2 to 5 ton systems. All models use an ECM motor and a factory-installed hard shut-off TXV metering device for R-410A refrigerant only.
The manual gives location and clearance requirements, heater package information, upflow/downflow/horizontal installation, air ducts, electrical connections, refrigerant tubing and metering devices, condensate drains, accessories, sequence of operations, start-up procedure, care and maintenance, airflow performance tables and an R-410A quick reference guide.
| Refrigerant | R-410A only |
|---|---|
| Motor type | ECM |
| Metering device | Factory-installed hard shut-off TXV |
| FEM4P cooling capacity | 1-1/2 to 4 tons (18,000 to 48,000 BTUH) |
| FEM4X/FXM/REM4X cooling capacity | 1-1/2 to 5 tons (18,000 to 60,000 BTUH) |
| Cabinet leakage at 0.5 inches W.C. | Less than 2% |
| Heater package sizes | 3kW through 30kW |
They are for R-410A refrigerant only.
No clearance (0 inches) is required from the supply duct to combustibles after the first 3 feet.
Yes, a field-fabricated auxiliary drain pan with a separate drain is required for installations over a finished living space.
All models use an ECM motor.