This is a manual of FM series hardware system, which introduces the system architecture, hardware composition structure, hardware device list, hardware configuration description, control cabinet installation and layout, main controller and power supply installation, I/O device installation, power system and grounding requirements, main controller module, system power module, PROFIBUS-DP bus and equipment
The Hollysys FM Series is a fieldbus-based main controller and distributed I/O system featuring independent communication nodes per I/O module, offering advanced, reliable, and easy-to-use characteristics. The system architecture comprises main controllers, power supplies, distributed I/O, terminal modules, and cabinets, interconnected via Industrial Ethernet (SNET) and PROFIBUS-DP (CNET) networks.
The manual details hardware components including main controller modules (FM801/FM803), power modules (FM910/FM920), communication modules (FM1200/FM1201/FM1202), various I/O modules (analog, digital, pulse, special function), terminal bases, extended terminal boards, and control cabinets (FP040/FP041/FP033/FP035/FP036/FP038). It provides installation guidelines, wiring, power supply and grounding requirements, and hardware configuration principles. This manual is written in Chinese.
| Main Controller FM801 Processor | Embedded x86 100 MHz |
|---|---|
| Main Controller FM803 Processor | Embedded x86 266 MHz |
| Power Module FM910 Output | 24 VDC ±10%, 180 W max |
| Power Module FM920 Output | 48 VDC ±10%, 150 W max |
| Analog Input Module FM148A Range | 0–10 V, 0–20 mA |
| Digital Input Module FM161D Voltage | 24 VDC |
| Control Cabinet FP040 Dimensions | 807×2175×652 mm (W×H×D) |
| Control Cabinet FP041 I/O Capacity | 84 slots |
The main controller uses an embedded fanless design with ultra-low power consumption of 7.5 W at 24 VDC.
The main control cabinet measures 807 mm wide, 2175 mm high, and 652 mm deep.
Yes, both the main controller and I/O modules support hot-swapping.