This is a basic operation manual for Hitachi P1 frequency converter, applicable to Detroit hoist program version v27 or higher
This manual is the Hitachi P1 basic instruction manual written for the Detroit Hoist program version 27 or greater. It begins by showing how to confirm the program number in VFD parameter db-02 before using the manual, then moves through basic specifications, power circuit wiring and control circuit wiring for the P1 inverter.
The rest of the document explains how to configure the speed control method and speeds/frequencies, set acceleration and deceleration times, use multi-step speed commands and hoist over-weight functions, and set up encoder-based limits and EZCOM communication for tandem hoists. It closes with parameter monitoring, fault code descriptions and troubleshooting procedures for faults such as E50, E51, E52, E53 and E054.
| Input power | 3-phase 50/60 Hz (recommended) |
|---|---|
| Voltage (400 V class models) | 380-480 Vac |
| Voltage (200 V class models) | 208-240 Vac |
| Digital I/O voltage | 24 Vdc (27 Vdc max) |
| Ambient temperature | -10 to 50 °C (14 to 122 °F) |
| Protection rating | IP20 – UL Open Type |
| Overload current rating | 150% for 60 s / 200% for 3 s |
| Built-in dynamic braking chopper | Up to 37 kW models |
Power up the VFD, open the scroll menu, go to the d:Monitor group and press the #2 button to move to the db group; the program number is shown in parameter db-02 and must be 27 or greater.
They come factory pre-configured for 2-Step speed control unless otherwise specified when ordering.
The overload current rating is 150% for 60 seconds and 200% for 3 seconds.
Speed and frequency values are stored as whole numbers, for example 15.25 Hz is stored as 1525.