Benchmark Boilers Models 750 through 6000 BMK Series Boilers Pre-Installation Gas Supply Guide

This manual is a gas supply design guide for AERCO Benchmark models 750 through 6000 BMK series boilers.


Benchmark Boilers Models 750 through 6000 BMK Series Boilers Pre-Installation Gas Supply Guide - cover page
Brand
Aerco
Category
Other
Document type
Service Manual
Language
English
Pages
17
File format
PDF
File size
1001 KB
Published
26 October, 2023
Updated
26 October, 2023
MD5 checksum
2DA1D1155C93711574DCC76C134B1F2B

About this manual

This document serves as a pre-installation gas supply design guide for AERCO Benchmark Low NOx gas-fired boilers, specifically Models 750 through 6000. It outlines the necessary gas train components, including safety shutoff valves and air/fuel valves, to ensure efficient combustion and safe operation. The guide emphasizes the importance of adhering to specified gas pressure requirements and local authority regulations during the design and installation phases.

What's inside

  • Safety Precautions
  • Gas Train Components
  • Gas Pressure Requirements
  • Manual Shutoff Valves
  • Pressure Regulators
  • Custom Gas Trains
  • Venting of Gas Supply Regulators
  • Drip Legs
  • Regulator Sizing
  • Installation Recommendations

Specifications

Regulator Sizing Volume (BMK4000)4000 – 4500 CFH

Frequently asked questions

Is an external manual shutoff valve required?

Yes, an external manual shutoff valve must be installed at each Benchmark boiler.

When is a lock-up type pressure regulator required?

An external lock-up type regulator is required where gas supply pressure will exceed 14.0" W.C. (3.49 kPa).