The document introduces the product information, installation, operation and maintenance guidelines of SG2K-S/SG2K5-S/SG3K-S/SG3K-D/SG5K-D/SG8K-D type photovoltaic inverters, and details the features and characteristics of the product
This manual provides detailed instructions for installing, operating, and maintaining Sungrow’s 1-phase grid-connected inverters, including models SG2K-S, SG2K5-S, SG3K-S, SG3K-D, SG5K-D, and SG8K-D. It covers safety precautions, electrical connections, commissioning, LCD operation, troubleshooting, and technical specifications. The document is intended for qualified personnel and inverter owners who will interact with the equipment. Safety warnings and hazard symbols are prominently featured to prevent injury or equipment damage.
The manual includes sections on mechanical mounting, electrical connection procedures, commissioning steps, LCD panel controls, and system decommissioning. Technical data for each model series is provided in the appendix, including input/output parameters, voltage ranges, and current limits. Safety guidelines emphasize proper grounding, voltage verification, and handling of high-voltage DC components.
| Max. PV input power | 3000 W / 3200 W / 4000 W |
|---|---|
| Max. PV input voltage | 600 V |
| Nominal AC output power | 2000 W / 2500 W / 3000 W |
| Max. AC output apparent power | 2000 VA / 2500 VA / 3000 VA |
| Nominal AC voltage | 230 Vac (single phase) |
| Grid frequency range | 45 Hz–55 Hz / 55 Hz–65 Hz |
| Total harmonic distortion (THD) | < 3 % (of nominal power) |
The maximum output over-current protection is 25 A.
The AC voltage range is 180 Vac–276 Vac (may vary with grid standards).