Motortronics MVC Plus Medium Voltage Soft Starter User Manual

This document is the MVC Plus user manual, which mainly introduces the features and characteristics of the product, including specifications, design features, working principle, protection functions, circuit board layout, etc.


Motortronics MVC Plus Medium Voltage Soft Starter User Manual - cover page
Brand
MOTORTRONICS
Category
Motor
Document type
User Manual
Language
English
Pages
78
File format
PDF
File size
1.7 MB
Published
19 October, 2023
Updated
19 October, 2023
MD5 checksum
B0D1D01A36514DCB47A35CB2E7E69771

About this manual

This manual provides instructions for the Motortronics MVC Plus, a Reduced Voltage Solid State Soft Starter designed for the starting, protection, and control of AC medium voltage motors. The device is an SCR-based controller that creates a complete Class E2 medium voltage motor Soft Starter when interfaced with an enclosure.

What's inside

  • Introduction
  • Specifications
  • Connections
  • Start-Up
  • User Interface and Menu Navigation
  • Setpoint Programming
  • Metering Pages
  • Maintenance and Troubleshooting

Specifications

Unit Running Overload Capacity (Continuous)125% of motor FLA
Unit Running Overload Capacity (30 seconds)500% of motor FLA
Frequency50 or 60Hz
Power Circuit SCR Count6, 12, or 18 SCRs
SCR Peak Inverse Voltage Ratings6500V - 19500V
Ambient Temperature Range0° to 40°C
Relative Humidity5 - 95%
Maximum Altitude3300 ft. (1000m)
Control Voltage2 or 3 wire 120VAC
Auxiliary Contacts Rating5 Amps, 240VAC max
BIL Rating2300V - 7200V
ProtocolModbus RTU
Signal TypeRS-485, RS-422 or RS232
Maximum Network Devices247 devices

Frequently asked questions

What is the MVC Plus designed for?

It is designed for the starting, protection, and control of AC medium voltage motors.

What is the maximum continuous overload capacity?

The unit has a continuous running overload capacity of 125% of the motor Full Load Amperage (FLA).

What frequency options are available?

The controller supports 50 or 60Hz frequencies, which are hardware selectable.

What is the ambient temperature range for enclosed units?

Enclosed units are designed for an ambient temperature range of 0° to 40°C (32° to 104°F).