This document is the MVC Plus user manual, which mainly introduces the features and characteristics of the product, including specifications, design features, working principle, protection functions, circuit board layout, etc.
This manual provides instructions for the Motortronics MVC Plus, a Reduced Voltage Solid State Soft Starter designed for the starting, protection, and control of AC medium voltage motors. The device is an SCR-based controller that creates a complete Class E2 medium voltage motor Soft Starter when interfaced with an enclosure.
| Unit Running Overload Capacity (Continuous) | 125% of motor FLA |
|---|---|
| Unit Running Overload Capacity (30 seconds) | 500% of motor FLA |
| Frequency | 50 or 60Hz |
| Power Circuit SCR Count | 6, 12, or 18 SCRs |
| SCR Peak Inverse Voltage Ratings | 6500V - 19500V |
| Ambient Temperature Range | 0° to 40°C |
| Relative Humidity | 5 - 95% |
| Maximum Altitude | 3300 ft. (1000m) |
| Control Voltage | 2 or 3 wire 120VAC |
| Auxiliary Contacts Rating | 5 Amps, 240VAC max |
| BIL Rating | 2300V - 7200V |
| Protocol | Modbus RTU |
| Signal Type | RS-485, RS-422 or RS232 |
| Maximum Network Devices | 247 devices |
It is designed for the starting, protection, and control of AC medium voltage motors.
The unit has a continuous running overload capacity of 125% of the motor Full Load Amperage (FLA).
The controller supports 50 or 60Hz frequencies, which are hardware selectable.
Enclosed units are designed for an ambient temperature range of 0° to 40°C (32° to 104°F).