This manual provides an overview, specification, design features, theory of operation, protection measures, electronic components and connection methods of MVC4 series soft starters.
This manual provides detailed instructions for installing, configuring, and operating the MVC4 soft starter, an SCR-based controller for medium voltage AC motors. It includes sections on specifications, wiring, user interface, setpoint programming, metering, and troubleshooting. The device supports programmable acceleration and deceleration, overload protection, and communication via Modbus RTU. Maintenance procedures and failure analysis are also covered.
The manual is organized into chapters covering introduction, connections, start-up, user interface, setpoint programming, metering, and maintenance. It includes reference charts, diagrams, and detailed explanations of features like thermal overload protection, phase imbalance detection, and event recording.
| AC Supply Voltage | 1000 – 7200VAC +10 to – 15% (Model dependent) |
|---|---|
| Unit Running Overload Capacity | 125% - Continuous 500% - 60 seconds, 600% - 30 seconds. 1 Cycle: Up to 14x FLA |
| Frequency | 50 or 60Hz, +2Hz hardware selectable |
| SCR Peak Inverse Voltage Ratings | 4500V - 19500V (Model dependent see Table 1) |
| Control Voltage | 120VAC (Customer supplied) |
| Auxiliary Contacts | Multiple: Form C (Contacts), rated 5 Amps, 240VAC max. 8 Relays (4 programmable): Form C contacts |
| BIL Rating | 1000V – 30KV , 2300V - 7200V 60KV |
| Overload Reset | Manual Retentive Thermal Memory |
| Phase Current Imbalance Protection | Imbalance Trip Level: 5 - 30% current between any two phases |
| Over Current Protection | Trip Level: 100 - 300% of motor FLA |
| Load Loss Trip Protection | Under Current Trip Level: 10 -90 % of motor FLA |
| Coast Down Lockout Timer | Coast Down Time Range: 1 - 60 minutes |
| Starts-per-hour Lockout Timer | Range: 1 - 6 successful starts per hour |
| Serial Communication Protocol | Modbus RTU |
| Operator Interface | LCD Readout Alpha numeric LCD display Keypad 8 function keys with tactile feedback |
| Clock and Memory | Real Time Clock Lithium ion battery for clock memory only |
1000 – 7200VAC +10 to – 15% (Model dependent).
Two Stage Electronic Overload Curves with programmable starting and running classes, manual retentive thermal memory, and dynamic reset capacity.
Modbus RTU protocol via RS-485, RS-422, or RS232.
It includes an alpha-numeric LCD display, 8 function keys with tactile feedback, and 12 LEDs for status indicators.