This manual provides an overview, specification, design features, theory of operation, protection measures, electronic components and connection methods of MVC4 series soft starters.


MCV4 Series Soft Starter User Manual - cover page
Brand
MOTORTRONICS
Document type
User Manual
Language
English
Pages
107
File format
PDF
File size
2.7 MB
Published
19 October, 2023
Updated
19 October, 2023
MD5 checksum
8A1B26A27A19ED71B506E701417B1F3A

About this manual

This manual provides detailed instructions for installing, configuring, and operating the MVC4 soft starter, an SCR-based controller for medium voltage AC motors. It includes sections on specifications, wiring, user interface, setpoint programming, metering, and troubleshooting. The device supports programmable acceleration and deceleration, overload protection, and communication via Modbus RTU. Maintenance procedures and failure analysis are also covered.

The manual is organized into chapters covering introduction, connections, start-up, user interface, setpoint programming, metering, and maintenance. It includes reference charts, diagrams, and detailed explanations of features like thermal overload protection, phase imbalance detection, and event recording.

What's inside

  • Introduction
  • Connections
  • Start-Up
  • User Interface and Menu Navigation
  • Setpoint Programming
  • Metering Pages
  • Maintenance and Troubleshooting

Specifications

AC Supply Voltage1000 – 7200VAC +10 to – 15% (Model dependent)
Unit Running Overload Capacity125% - Continuous 500% - 60 seconds, 600% - 30 seconds. 1 Cycle: Up to 14x FLA
Frequency50 or 60Hz, +2Hz hardware selectable
SCR Peak Inverse Voltage Ratings4500V - 19500V (Model dependent see Table 1)
Control Voltage120VAC (Customer supplied)
Auxiliary ContactsMultiple: Form C (Contacts), rated 5 Amps, 240VAC max. 8 Relays (4 programmable): Form C contacts
BIL Rating1000V – 30KV , 2300V - 7200V 60KV
Overload ResetManual Retentive Thermal Memory
Phase Current Imbalance ProtectionImbalance Trip Level: 5 - 30% current between any two phases
Over Current ProtectionTrip Level: 100 - 300% of motor FLA
Load Loss Trip ProtectionUnder Current Trip Level: 10 -90 % of motor FLA
Coast Down Lockout TimerCoast Down Time Range: 1 - 60 minutes
Starts-per-hour Lockout TimerRange: 1 - 6 successful starts per hour
Serial Communication ProtocolModbus RTU
Operator InterfaceLCD Readout Alpha numeric LCD display Keypad 8 function keys with tactile feedback
Clock and MemoryReal Time Clock Lithium ion battery for clock memory only

Frequently asked questions

What is the AC supply voltage range for the MVC4?

1000 – 7200VAC +10 to – 15% (Model dependent).

What are the overload protection features?

Two Stage Electronic Overload Curves with programmable starting and running classes, manual retentive thermal memory, and dynamic reset capacity.

What communication protocol does the MVC4 support?

Modbus RTU protocol via RS-485, RS-422, or RS232.

What is the operator interface like?

It includes an alpha-numeric LCD display, 8 function keys with tactile feedback, and 12 LEDs for status indicators.