Goodman TP-107M Long Line Set Application Guide

This document is about Goodman air conditioner long pipe installation guide, including installation requirements and additional accessories


Goodman TP-107M Long Line Set Application Guide - cover page
Brand
Goodman
Category
Air conditioner
Document type
Installation Guide
Language
English
Pages
12
File format
PDF
File size
340 KB
Published
19 October, 2023
Updated
19 October, 2023
MD5 checksum
27A7234CDCC5AD9CB5F54FE6D3BC6CC9

About this manual

This technical publication provides installation instructions for Goodman AHRI listed R-410A air conditioner and heat pump split systems with nominal capacities of 18,000 to 60,000 Btuh. The guide specifically addresses applications where the line set exceeds 80 feet (24.4 m) in actual length, covering three different configurations based on the relative elevation of the outdoor and indoor units.

What's inside

  • General Requirements
  • Same Elevation Installation
  • Outdoor Unit Above Indoor Unit
  • Outdoor Unit Below Indoor Unit
  • Calculations
  • Tubing Equivalent Length
  • Tube Size
  • Refrigerant Charge
  • Accessory Requirements
  • Vibration and Noise

Specifications

Nominal Capacity Range18,000 to 60,000 Btuh
Refrigerant TypeR-410A
Minimum Line Set Length80 feet (24.4 m)
Maximum Equivalent Length (Scroll/Reciprocating)250 feet (76.2 m)
Maximum Equivalent Length (Rotary)150 feet (45.7 m)
Required Liquid Line Size3/8"
Required Subcooling7 to 9 ºF

Frequently asked questions

What refrigerant type is covered by this guide?

The guide applies to AHRI listed R-410A air conditioner and heat pump split systems.

When is a crankcase heater required?

A crankcase heater must be installed on any compressor if one is not already factory installed.

What is the maximum equivalent length for units with rotary compressors?

The maximum equivalent length is 150 feet (45.7 m) for single stage units with rotary compressors.

Is a thermostatic expansion valve (TXV) required?

Yes, the use of a thermostatic expansion valve (TXV) is required in all long line set applications.