This manual introduces the instructions for use of the precharged expansion tanks, including safety instructions, function descriptions, and operating limits.
This manual provides safety instructions and operational limits for B&G precharged expansion tanks, which contain a bladder or diaphragm to separate air from system water. These tanks are designed for closed-loop heating and cooling systems only and are not for use in domestic or potable water systems due to corrosion risks.
| Maximum Operating Pressure | 125 psi |
|---|---|
| Maximum Operating Temperature | 240ºF |
| Minimum Operating Temperature (non-glycol) | 35°F |
| Minimum Operating Temperature (glycol) | 18°F |
No, they are not for use in domestic, potable, or fresh water systems as this can cause serious corrosion and potential explosion.
Series 'B', 'D', and 'B-LA' are for use in closed loop systems only.
No, Series B-LA tanks must be installed in a vertical position and cannot be installed horizontally.