Describes the functions and configuration of the Gamewell-FCI 7200 driver
This manual provides instructions for configuring and using the MSA Safety FCI 7200 Series System Control Unit driver with FieldServer. It details hardware connections, data array parameters, and client-side configuration. The driver is passive and does not poll or send commands to the SCU. Manual panel synchronization is required via reset. It supports firmware versions prior to 2.20 and 3-line messages from 2.20 onward, requiring a 20-character System ID for 3-line messages.
| Max Nodes Supported (Client Mode) | 1 Node per serial port |
|---|---|
| Baud Rate | 1200 |
| Data Bits | 8 |
| Stop Bits | 1 |
No, the driver cannot send data or commands to the SCU. It only processes received messages.
Manual synchronization is required. Push the reset button on the panel to transmit a reset message, which clears the FieldServer data and triggers re-synchronization.
It supports firmware versions earlier than 2.20 and 3-line messages from 2.20 onward, requiring a 20-character System ID for 3-line messages.