MSA Safety CEI-ABI Driver User Manual

This manual provides an overview of the Notifier CEI-ABI Driver for EN.54 exchanges.


MSA Safety CEI-ABI Driver User Manual - cover page
Brand
MSA Safety
Category
Automation control Equipment
Document type
User Manual
Language
English
Pages
21
File format
PDF
File size
693 KB
Published
17 October, 2023
Updated
17 October, 2023
MD5 checksum
A08DCF961A273BFDDA838465AED3D367

About this manual

This manual describes the CEI-ABI driver for MSA Safety's FieldServer, enabling data transfer to and from EN.54 fire alarm exchanges via RS-232 or RS-485. It covers hardware connections, configuration parameters, and data array setup. The driver supports 80 zones and 16 loops, with point and zone mapping, event handling, and data tap functionality. Configuration includes alignment modes for zones, loops, and analogs, followed by normal polling for event data.

What's inside

  • Description
  • Driver Scope of Supply
  • Hardware Connections
  • Data Array Parameters
  • Client Side Configuration
  • Server Side Configuration
  • Configuring the FieldServer as a CEI-ABI Data Tap
  • Useful Features
  • Vendor Information
  • Reference

Specifications

ProtocolCEI-ABI
Connection TypesRS-232 or RS-485
Zones80
Loops16
Points per Exchange3,168
Point Status Values0 = NORMAL, 1 = ALARM, 7...14 = TROUBLE, 57 = not installed, 61, 67 = disabled, 70 = ON, 71 = OFF
Analog Values0 to 255
Data ArraysCounts_1, Pnt_sts_1, Pnt_faults_bmap_1, Pnt_analogs_1, Pnt_Dev_codes_1, Pnt_Evt_codes_1, Zone_sts_1, Zn_Dev_codes_1, Zn_Evt_codes_1, Zone_labels_1, Zone_pnt_sts_1, Zone_setup_1, Reset_1, Analogs_1_0

Frequently asked questions

What protocol does the CEI-ABI driver use?

The CEI-ABI driver uses the CEI-ABI protocol to transfer data to and from EN.54 exchanges over RS-232 or RS-485.

How many zones and loops does the driver support?

The driver supports 80 zones and 16 loops.

What are the point status values?

Point status values are: 0 = NORMAL, 1 = ALARM, 7...14 = TROUBLE, 57 = not installed, 61, 67 = disabled, 70 = ON, 71 = OFF.

What is the purpose of the Data Arrays?

Data Arrays are protocol neutral data buffers for storage of data to be passed between protocols. They are declared with data format, length, and name.