Lapp Automaatio EPIC SENSORS Flanged Temperature Sensor Type T-F / W-F Installation and User Manual

This manual describes the technical data, installation instructions and use of EPIC® SENSORS flanged temperature sensors by Lapp Automaatio Oy.


Lapp Automaatio EPIC SENSORS Flanged Temperature Sensor Type T-F / W-F Installation and User Manual - cover page
Brand
Lapp Automaatio
Category
Industrial Robot
Document type
User Manual
Language
English
Pages
23
File format
PDF
File size
859 KB
Published
18 October, 2023
Updated
18 October, 2023
MD5 checksum
5FA41B393C019A8653F35794DC29F8F1

About this manual

This document serves as the installation and user manual for Lapp Automaatio EPIC SENSORS flanged temperature sensors, specifically models Type T-F (thermocouple) and Type W-F (resistance). The sensors are constructed according to DIN 43772 form 2F and are designed for industrial measuring applications where the thermowell can be removed and replaced during maintenance. They feature mineral insulated (MI) elements and are available with ceramic connection blocks or open wire ends.

What's inside

  • Product description and intended use
  • Temperatures, measuring
  • Temperatures, ambient
  • Code key
  • Technical data
  • Materials
  • Installation instructions and example
  • Coatings
  • Tightening torques
  • Opening the connection head

Specifications

Measuring range (Pt100)-200…+ 550 °C
Measuring range (TC)-200…+ 1200 °C
Ambient temperature (without transmitter)-40…+135 °C
Connection head material (Standard/Ex i)Aluminum
Connection head material (Ex d)Aluminum or Stainless Steel
Sensor element sheath (Pt100)AISI 316L
Sensor element sheath (TC)Inconel 600 or AISI 316L
Flange materialAISI 316L

Frequently asked questions

What are the standard measuring elements for Type T-F and W-F sensors?

The standard version for Type T-F is a K-type thermocouple, and for Type W-F it is a 4-wire Pt100.

Can the measuring elements be changed without removing the sensor?

Yes, the measuring elements are mineral insulated (MI) elements which can be changed on the fly.

Which hazardous area approvals are available for these sensors?

The sensors are available as ATEX and IECEx approved protection types Ex d and Ex i.