This document is the instruction manual of EE160 sensor. It is mainly used for measuring humidity and temperature in HVAC system.
This manual provides instructions for the E+E Elektronik EE160 transmitter, a device designed for measuring humidity and temperature in HVAC applications. It covers wall or duct mounting, connection diagrams for various output types (Modbus RTU, BACnet MS/TP, 4...20 mA, 0...10 V), and general usage precautions.
| Measured values | relative humidity, temperature |
|---|---|
| Humidity sensor | E+E Sensor HCT01-00D |
| Working range (RH) | 10...95% RH |
| Temperature accuracy | ±0.3°C at 20°C |
| Humidity accuracy | ±2.5% RH at 20°C |
| Operating temperature | -40...60°C |
| Protection class | IP65 / NEMA 4 |
| Power supply (0-10 V / RS485) | 15 - 35V DC or 24V AC ±20% |
| Housing material | Polycarbonate, UL94V-0 approved |
The working range for relative humidity is 10...95% RH.
Yes, the EE160 transmitter is available for wall or duct mounting.
The factory setting for the Slave-ID is 245 as an integer 16Bit value.
The filter cap shall be replaced once in a while if employed in dusty, polluted environments.