This manual describes the function and operation of E+E Electronics' EE371 dew point transmitter/switch.
The E+E Elektronik EE371 is a device designed for measuring dew point temperature (Td), frost point temperature (Tf), and volume concentration (Wv) in air and other non-corrosive, non-flammable gases. The device is available in two models: the transmitter (Modell t) with selectable analogue outputs and the switch (Modell S) with relay outputs for control and alarm purposes. It features an auto-calibration procedure that runs every 30 minutes to ensure high-precision measurements, particularly in low dew point ranges.
| Measurement Range | Dew point temperature (Td), frost point temperature (Tf) and volume concentration (Wv) |
|---|---|
| Max Pressure | 20 bar (290 psi) for air; 100 bar (1450 psi) for other gases |
| Auto-calibration Interval | Every 30 minutes |
| Auto-calibration Duration | Approx. 3 minutes |
| Analogue Output Scaling Range | -100...80 °C (-148...176 °F) |
| Accuracy | ≤ ±2 °C |
The device is capable of measuring down to -60 °C.
Installation, electrical connection, maintenance and commissioning shall be performed by qualified personnel only.
During auto-calibration, the analogue outputs are frozen at the last measured value.