This document is a user manual for testo 316-3 Leakage detector for refrigerants. It introduces the features, functions, usage, and maintenance of the product.
This manual provides instructions for using the Testo 316-3 leakage detector to identify refrigerant leaks in HVAC systems. It includes safety precautions, product specifications, and operational steps for commissioning and leak detection. Maintenance and disposal guidelines are also covered.
The device uses an electrochemical sensor with a heated diode to detect various refrigerants, including HFCs, HCFCs, and CFCs. It features visual and audible alerts, a flexible probe shaft, and a battery-powered design with a 16-hour operational life.
| Sensor | Electrochemical sensor with heated diode |
|---|---|
| Detectable Refrigerants | All HFCs, HCFCs and CFCs e.g. FX80, 112A, R11, R114, R12, R123, R1234yf, R1234ze, R124, R125, R12a, R13, R134a, R13B1, R14, R142b, R161, R22, R227, R23, R236fa, R245fa, R32, R401A, R401B, R401C, R402B, R403B, R404A, R406A, R407A, R407B, R407C, R407D, R407F, R408A, R409A, R410A, R411A, R412A, R413A, R414B, R416A, R417A, R417B, R417C, R420A, R421A, R421B, R422A, R422B, R422C, R422D, R424A, R426A, R427A, R434A, R437A, R438A, R448A, R449A, R452A, R500, R502, R503, R507, RS08A, R508B, R1233zd, R450A, R455A, R513A, R407H, R444B, R452B, R453a, R454A, R454B, R454C, R458A, SP22 |
| Response Threshold | <4 g/a/ <0.15 oz/a |
| Sensor Service Life | 80-100 hours (equates to approx. 1 year of normal usage) |
| Warm-up Period | Approx. 20s |
| Power Supply | Alkaline Batteries (2xD) |
| Battery Life | 16 hours |
| Operating Conditions | -18 to 50 °C / -O to 122 °F 20 % - 80 %RH, non-condensing |
| Minimum Response Time | <1 second |
| Recovery Time for 50 g/yr Exposure | 12 seconds |
| Calibration Frequency | Check annually with Calibration Standard |
| Weight | Approx. 400 g (incl. batteries) |
| Dimensions (L x W x H) | Housing: approx. 270 x 65 x 65 mm; Length of flexible sensor shaft including sensor head: approx. 285 mm |
| EC Directives | 201 4/30/EC |
| Standards | EN14624:2012 |
It detects all HFCs, HCFCs and CFCs, including specific types like R134a, R410A, R407C, and R507.
The response threshold is less than 4 g/a or less than 0.15 oz/a.
The battery life is approximately 16 hours.
It operates between -18 to 50 °C and 20 % to 80 %RH, non-condensing.