This manual introduces the basic functions and usage methods of the EIM 2000 series M2CP Digital Futronic module. This manual mainly includes the introduction of the module's features, specifications, installation and wiring, module setup and calibration, etc.
This manual provides instructions for installing, wiring, and configuring the EIM 2000 Series M2CP Digital Futronic module. It details how to set up analog input/output, calibrate position, and configure control modes for different motor types. The module converts 4-20mA signals to digital control and back to analog feedback, with built-in auto-tuning and protection features.
The manual includes sections on indicator lights, DIP switch settings, calibration procedures, and wiring guidelines for analog signals, including isolation and loop power requirements.
| Isolated Analog Input | 4-20mA with 12-bit (.025%) resolution (calibration range of 0-24mA) |
|---|---|
| Isolated Analog Output | 4-20mA with 16-bit (.0015%) resolution (calibration range of 0-24mA) |
| Control Accuracy - Futronic II | +/- 1.0% @ 15 second stroke time or greater |
| Operating Temperature Range | -40C to +85C (-40F to +185F) |
Press UP to set Span (20mA) Input and DOWN to set Zero (4mA) Input while S1 is ON.
The Digital Futronic module converts 4-20mA analog input to digital for processing and from digital to 4-20mA analog output for position feedback.
Futronic II Electro-mechanical AC motor starter, Futronic III SCR Solid-state DC motor starter, Futronic IV Triac Solid-state (SSR) AC motor starter.
2500V AC for 1 Minute (Input to output and I/O to ground).