A.A.C. SHP Series Split System Heat Pump Outdoor Section Installation and Maintenance Instructions

This file is about the installation and maintenance instructions of the outdoor section of the SHP series split system heat pump


A.A.C. SHP Series Split System Heat Pump Outdoor Section Installation and Maintenance Instructions - cover page
Brand
AAC
Category
Other
Document type
Installation Guide
Language
English
Pages
11
File format
PDF
File size
144 KB
Published
17 October, 2023
Updated
17 October, 2023
MD5 checksum
D8DED39AA5C3983987FA664EF9B99CCE

About this manual

This manual provides instructions for the installation and maintenance of the A.A.C. SHP Series split system heat pump outdoor section. It details requirements for location, foundation, and refrigerant tubing connections, emphasizing safety precautions regarding electrical shock and refrigerant pressure.

What's inside

  • Installation
  • Start-Up
  • Operation
  • Maintenance
  • Wiring Diagrams
  • Warranty
  • Application Limitations
  • Refrigerant Tubing Connection
  • Electrical Wiring
  • Low Pressure Switch

Specifications

Maximum elevation difference20 feet
Maximum total line length50 feet
Minimum foundation height3 inches

Frequently asked questions

Who should install this equipment?

The equipment must be installed by trained and experienced service and installation technicians.

What is the factory charge adjustment rate for additional line length?

Adjust the charge at 0.60 oz. per foot of 3/8" liquid line and 1.2 oz. per foot of 1/2" line.

What are the low pressure switch settings?

The pressure control opens at 10 psi and resets at 30 psi.