This manual introduces the basic use of the Hitachi L100-M series inverter, including circuit parameters, terminal descriptions, and operating instructions.
This document serves as a quick reference guide for experienced users maintaining existing installations of the Hitachi L100-M Series Inverter. It provides essential information regarding power circuit terminals, control circuit terminal descriptions, and related technical parameters. The guide is intended for reference use only and directs users to the main L100 Inverter Manual for initial installation instructions and safety warnings.
| Logic Input Supply | 24VDC supply, 30 mA max. |
|---|---|
| Logic Input Voltage | 27VDC max. |
| Logic Output Current | 50 mA max. ON current |
| Analog Input Voltage Range | 0 to 9.6 VDC |
| Analog Output Voltage Range | 0 to 10VDC |
| Relay Contact Rating (Resistive) | 250V AC, 2.5A |
| Over-current Trip Threshold | 200% of rated current |
This guide is intended for reference use by experienced users in servicing existing installations.
Press the Stop/Reset key to reset the inverter and clear the error.
It is ON when the inverter output is ON and the motor is developing torque, and OFF when the inverter output is OFF.