Pressure Systems Pressure Test Procedures SLAC-I-730-0A21C-033-R004

Describes the purpose, procedures, and methods of pressure testing pressure systems


Pressure Systems Pressure Test Procedures SLAC-I-730-0A21C-033-R004 - cover page
Document type
Other
Language
English
Pages
8
File format
PDF
File size
380 KB
Published
16 October, 2023
Updated
16 October, 2023
MD5 checksum
258D18183846FC8403351BCBD80B0BD4

About this manual

This document outlines the Environment, Safety & Health Division's procedures at SLAC National Accelerator Laboratory for conducting pressure tests. It details requirements for both hydrostatic (water) and pneumatic (air/gas) testing methods to ensure system safety, reliability, and leak tightness before use or after repair.

What's inside

  • Purpose
  • Hydrostatic Testing
  • Pneumatic Testing
  • Test Procedure Steps
  • Recording Requirements
  • Test Pressure Codes
  • Table of Test Pressures

Frequently asked questions

What is the required test pressure for a new pressure vessel undergoing a hydrostatic test?

The test pressure must be 1.3 times the maximum allowable working pressure (MAWP) of the vessel.

What is the minimum duration for a hydrostatic test of a building service system?

The system must be held at test pressure for a minimum of 10 minutes.

What is the maximum allowable pressure for a pneumatic test of process piping without special approval?

The pressure must not exceed 150 psig.