PDI PowerPak Power Distribution Unit Guide Specifications (Revision 002, 6/1/2017) describes requirements for a power distribution unit (PDU) distributing power to sensitive loads.
This document outlines the specifications for the PDI PowerPak Power Distribution Unit (PDU), a device designed to distribute power to sensitive loads. The PDU is certified through ETL for various standards, including UL 60950-1 and NFPA, and complies with FCC Part 15 EMI emission standards for Class A computing devices. It is designed, manufactured, tested, and installed in compliance with a comprehensive list of industry standards such as UL67, UL50, UL489, and IEEE 519-1991.
| kVA Rating | 50-300 kVA |
|---|---|
| Input Frequency | 60 Hz ± 5 Hz or 50 Hz ± 5 Hz |
| Operating Temperature | 0°C to 40°C |
| Storage Temperature | -36°C to +70°C |
| Relative Humidity | 0% to 95% non-condensing |
| Operating Altitude | Maximum 6,600 ft |
| Storage and Transport Altitude | Up to 40,000 ft |
| Warranty Period | 12 months after startup or 18 months after shipping |
| Cooling Method | Convection cooled, no fans |
| Enclosure Standard | NEMA-1, IP20 |
The PDU is certified through ETL for UL 60950-1 (PDU Standard) and CS 22.2.
No, the unit is convection cooled and has no fans.
The manufacturer provides a 12-month warranty against defects in material and workmanship.