this manual provides general information for properly installing and operating standard kooltronic hazardous location air conditioners (hl series).
The Kooltronic Hazardous Location Air Conditioners (HL Series) are designed to provide a cool, dehumidified environment for electronic components. The unit features a closed-loop design to ensure components are not exposed to hot, dirty operating conditions. This manual provides general information for properly installing and operating standard Kooltronic Air Conditioners, with specific mounting instructions and technical data found on pages 12 through 15.
The HL Series is designed for Class I, Division 1 and Division 2 applications and must be installed on pressurized customer enclosures connected to a Purge/Pressurized Control System. All electrical and electronic components are located in the pressurized evaporator enclosure, while mechanical components like the condenser blower are exposed to ambient air. The unit utilizes a floating type gate valve for the condensate drain system to prevent pressurized gas loss.
| Air Leakage | 18 CFM |
|---|---|
| Air Leakage | 0.36 IW.G. |
| Internal Pressurized Volume | 7.7 CU. FT. |
| Ambient Temperature | Min: Max: |
| Refrigerant | Factory Charge (6) . |
The air conditioner is designed to operate in a vertical position only and must be placed in this position a minimum of 5 minutes prior to operating.
Operating the unit if it is not in its designed mounting position or tipped more than 45 degrees will cause permanent compressor damage and void the warranty.
The minimum circuit ampacity should be at least 125% of the amperage found on the nameplate for the corresponding voltage.
No, the air conditioner must be properly installed on a pressurized enclosure and connected to the pressurized enclosure Purge/Pressurized Control System before operating.