Kooltronic HL Series Hazardous Location Air Conditioner Operator's Manual

this manual provides general information for properly installing and operating standard kooltronic hazardous location air conditioners (hl series).


Kooltronic HL Series Hazardous Location Air Conditioner Operator's Manual - cover page
Brand
Kooltronic
Category
Air conditioner
Document type
User Manual
Language
English
Pages
19
File format
PDF
File size
875 KB
Published
16 October, 2023
Updated
16 October, 2023
MD5 checksum
D96E5880552D5A3ADB4D0EE5F25C3639

About this manual

The Kooltronic Hazardous Location Air Conditioners (HL Series) are designed to provide a cool, dehumidified environment for electronic components. The unit features a closed-loop design to ensure components are not exposed to hot, dirty operating conditions. This manual provides general information for properly installing and operating standard Kooltronic Air Conditioners, with specific mounting instructions and technical data found on pages 12 through 15.

The HL Series is designed for Class I, Division 1 and Division 2 applications and must be installed on pressurized customer enclosures connected to a Purge/Pressurized Control System. All electrical and electronic components are located in the pressurized evaporator enclosure, while mechanical components like the condenser blower are exposed to ambient air. The unit utilizes a floating type gate valve for the condensate drain system to prevent pressurized gas loss.

What's inside

  • Introduction
  • Incoming Inspection
  • Product Handling
  • Product Identification and Nameplate
  • Warnings
  • Principles of Operation
  • Pre-Installation Testing
  • Mounting
  • Maintenance
  • Trouble Shooting

Specifications

Air Leakage18 CFM
Air Leakage0.36 IW.G.
Internal Pressurized Volume7.7 CU. FT.
Ambient TemperatureMin: Max:
RefrigerantFactory Charge (6) .

Frequently asked questions

What is the proper mounting position for the air conditioner?

The air conditioner is designed to operate in a vertical position only and must be placed in this position a minimum of 5 minutes prior to operating.

What happens if the unit is tipped more than 45 degrees?

Operating the unit if it is not in its designed mounting position or tipped more than 45 degrees will cause permanent compressor damage and void the warranty.

What are the electrical requirements for the circuit?

The minimum circuit ampacity should be at least 125% of the amperage found on the nameplate for the corresponding voltage.

Can the air conditioner be operated without a pressurized enclosure?

No, the air conditioner must be properly installed on a pressurized enclosure and connected to the pressurized enclosure Purge/Pressurized Control System before operating.