This is a quick installation guide that introduces the features and characteristics of the VertX V100 (CS) Door/Reader Interface Panel product and installation methods.
This guide provides step‑by‑step instructions for installing the HID V100 Door/Reader Interface panel. It includes preparation steps, hardware mounting, wiring of power, alarm inputs, readers, and RS‑485 connections, as well as configuration of interface addresses and output contacts.
Safety notes, cable specifications, and product specifications such as power requirements, current draw, operating temperature and humidity are also detailed to ensure proper and reliable operation in access‑control installations.
| Power Supply Voltage | 12‑16 VDC |
|---|---|
| Maximum Current (12 VDC) | 1 Amp |
| Average Operating Current (12 VDC, two readers) | 450 mA |
| Operating Temperature Range | 32°‑122 °F (0°‑50 °C) |
| Humidity Range | 5 % to 95 % non‑condensing |
| RS‑485 Cable Type | Belden 3105A, 22 AWG twisted pair, shielded 100Ω cable (or equivalent) |
The V100 operates from a 12‑16 VDC power supply.
It draws up to 1 Amp maximum, with an average of about 450 mA when two iCLASS readers are connected.
Use a 4000‑foot (1220 m) Belden 3105A, 22 AWG twisted‑pair shielded 100 Ω cable, or an equivalent cable.