The EE65 series is the ideal choice for accurate ventilation control applications. It is based on an innovative thermal film anemometer. The thin-film sensor from Endress+Hauser ensures high accuracy even at low air velocities, which cannot be achieved by conventional anemometers using standard temperature sensors or NTCs. In addition, this sensor is less sensitive to dust and dirt than other sensors, so measurements are more reliable and maintenance costs are low. The EE65 series offers current or voltage output signals, and users can select the measuring range and response time using jumpers. The lower angle dependence makes it easier and more economical to install. LCD displays and models with separate sensor probes are also available.
The Winner EE65 wind speed transmitter is designed for precise ventilation control applications, using an innovative thermal film anemometer. It offers high accuracy at low wind speeds and is less sensitive to dust and dirt compared to traditional sensors. The device supports current or voltage output, adjustable measurement range and response time via jumpers, and features low angle dependency for easier installation. Optional LCD display and separate probe models are available.
Technical specifications include a measurement range of 0–15 m/s, ±0.2 m/s + 3% accuracy, and a response time of 4 or 0.2 seconds. It operates on 24V AC/DC, consumes up to 150mA (AC) or 90mA (DC), and has an IP65 enclosure. Temperature ranges are -25°C to 50°C for the probe and -10°C to 50°C for the circuit board. This manual is written in Chinese.
| Measurement Range | 0...15m/s, 0...10m/s, 0...20m/s |
|---|---|
| Output | 0 - 10 V or 4 - 20 mA |
| Accuracy | ± (0.2m/s + 3%*mv) |
| Response Time | typ. 4 seconds or typ. 0.2 seconds |
| Power Supply | 24V AC/DC ± 20% |
| Current Consumption | Max 150mA (AC), Max 90mA (DC) |
| Angle Dependency | < 3% of measurement value (|Δα| < 10°) |
| Enclosure Rating | IP65 (Nema 4), IP40 (with LCD) |
| Probe Operating Temp | -25...50°C |
| Circuit Board Temp | -10...50°C |
| Cable Diameter | Ø 4.5 - 10 mm |
The measurement range is 0...15m/s, 0...10m/s, or 0...20m/s, selectable via jumpers.
It provides either 0–10 V or 4–20 mA output signals.
The response time is typically 4 seconds or 0.2 seconds, depending on the setting.
It operates on 24V AC/DC ± 20%.