Acuvim II series products are a comprehensive and accurate measurement data products, which can be widely used in the fields of electricity, electricity, electrical manufacturing, etc., and have many features, such as support for multiple measurement functions, high precision, etc.
This manual is for the Accuenergy Acuvim II series multifunction power meter. It covers product introduction, installation and wiring, panel operation, measurement and statistics functions, demand and harmonic data, alarms, I/O and communication modules, trend recording, and Modbus communication.
The appendices provide technical specifications, ordering information, and version information. The manual also lists the package contents and application areas for the meter. This manual is written in Chinese.
| Rated voltage | 400 LN / 690 LL Vac RMS (three-phase); 400 LN Vac RMS (single-phase) |
|---|---|
| Frequency range | 45-65 Hz |
| Overvoltage category and pollution degree | Category III, pollution degree II |
| Voltage overload | 1500 Vac continuous; 3250 Vac for 1 minute |
| Voltage input impedance | 2 MΩ per phase |
| Voltage startup value | 30 Vac |
| Rated current | 5 Amp AC |
| Current measurement range | 0-10 Amp AC |
| Current overload | 20 Arms continuous; 100 Arms for 1 s |
| Current burden | 0.05 VA typical at 5 Arms |
| Current startup value | 0.1% of rated value |
| Voltage and current accuracy | 0.2 class |
| Power and energy accuracy | 0.5 class (Acuvim IIR 0.2 class) |
| Active energy accuracy | 0.5S class (Acuvim IIR 0.2S class) |
| Reactive energy accuracy | Class 2 |
| Harmonic measurement | 2nd to 31st harmonics (Acuvim IIR 2nd to 63rd) |
The package includes one Acuvim II series meter, three pluggable terminal blocks, four mounting accessories, one gasket, one user manual, and one warranty card.
The listed applications include energy management systems, industrial automation, residential power monitoring, substation automation, distribution network automation, intelligent buildings, and intelligent distribution panels or switchgear.
Voltage and current measurement accuracy is 0.2 class.
Acuvim II measures 2nd to 31st harmonics, while Acuvim IIR measures 2nd to 63rd harmonics.