Datasheet for the Acuvim II series advanced power and energy meter with revenue-grade accuracy, multiple communication protocols, data logging, and flexible…
The Acuvim II series advanced power and energy meters provide power monitoring, kWh metering, and power quality analysis in a panel-mount or DIN-rail form factor. They support over 15 industrial communication protocols via plug-in expansion modules and offer dual Ethernet ports with RSTP daisy-chain capability.
Key features include revenue-grade accuracy (ANSI C12.20 class 0.1 and IEC 62053-22 class 0.1s), high-speed data logging up to 8GB with the WEB2 module, fast Modbus refresh rates down to 20ms, time-of-use tariff support, and compatibility with various current transformer types including Rogowski coils, 5A, 1A, mA, and 333mV outputs.
| Voltage Accuracy | 0.1% |
|---|---|
| Current Accuracy | 0.1% |
| Active Power Accuracy | 0.1% |
| Frequency Accuracy | 0.001% |
| Active Energy Class | Class 0.1s (IEC 62053-22), Class 0.1 (ANSI C12.20) |
| Harmonic Resolution | 63rd harmonic |
| Communication Protocols | Modbus RTU, BACnet MS/TP, Modbus TCP/IP, BACnet IP, IEC 61850, DNP 3.0, SNMP, HTTP/HTTPS, FTP, SMTP, MQTT, PROFIBUS DP |
| Current Input Options | 5A, 1A, 333mV, Rogowski Coil, 80mA/100mA/200mA |
| Voltage Input Range | 400Vac L-N, 690Vac L-L (+20%) |
| Control Power Range | 100~415Vac, 50/60Hz; 100~300Vdc |
| Operating Temperature | -25°C to 70°C |
| Standards Compliance | IEC 62053-22, ANSI C12.20, IEC 61557-12, IEC 61010-1, UL 61010-1, IEC 61000-4, CISPR 22, EN55011 |
The Acuvim II supports Modbus RTU and BACnet MS/TP via RS485, and with optional modules adds Modbus TCP/IP, BACnet IP, IEC 61850, DNP 3.0, SNMP, HTTP/HTTPS, FTP, SMTP, MQTT, and PROFIBUS DP.
Active energy meets IEC 62053-22 class 0.1s and ANSI C12.20 class 0.1 revenue-grade accuracy.
The meter is directly compatible with 5A, 1A, 80mA, 100mA, 200mA, 333mV, and Rogowski coil current transformers.
The operating temperature range is -25°C to 70°C (-13°F to 158°F).