Accuenergy Acuvim II Advanced Power & Energy Meter Datasheet

Datasheet for the Acuvim II series advanced power and energy meter with revenue-grade accuracy, multiple communication protocols, data logging, and flexible…


Accuenergy Acuvim II Advanced Power & Energy Meter Datasheet - cover page
Brand
AccuEnergy
Category
Monitoring Equipment
Document type
Datasheet
Language
English
Pages
12
File format
PDF
File size
1.5 MB
Published
15 November, 2026
Updated
15 November, 2026
MD5 checksum
96D9F6950CC8ABCF96023C245E64FA5A

About this manual

The Acuvim II series advanced power and energy meters provide power monitoring, kWh metering, and power quality analysis in a panel-mount or DIN-rail form factor. They support over 15 industrial communication protocols via plug-in expansion modules and offer dual Ethernet ports with RSTP daisy-chain capability.

Key features include revenue-grade accuracy (ANSI C12.20 class 0.1 and IEC 62053-22 class 0.1s), high-speed data logging up to 8GB with the WEB2 module, fast Modbus refresh rates down to 20ms, time-of-use tariff support, and compatibility with various current transformer types including Rogowski coils, 5A, 1A, mA, and 333mV outputs.

What's inside

  • DESCRIPTION
  • KEY FEATURES
  • SPECIFICATIONS
  • FUNCTION LIST

Specifications

Voltage Accuracy0.1%
Current Accuracy0.1%
Active Power Accuracy0.1%
Frequency Accuracy0.001%
Active Energy ClassClass 0.1s (IEC 62053-22), Class 0.1 (ANSI C12.20)
Harmonic Resolution63rd harmonic
Communication ProtocolsModbus RTU, BACnet MS/TP, Modbus TCP/IP, BACnet IP, IEC 61850, DNP 3.0, SNMP, HTTP/HTTPS, FTP, SMTP, MQTT, PROFIBUS DP
Current Input Options5A, 1A, 333mV, Rogowski Coil, 80mA/100mA/200mA
Voltage Input Range400Vac L-N, 690Vac L-L (+20%)
Control Power Range100~415Vac, 50/60Hz; 100~300Vdc
Operating Temperature-25°C to 70°C
Standards ComplianceIEC 62053-22, ANSI C12.20, IEC 61557-12, IEC 61010-1, UL 61010-1, IEC 61000-4, CISPR 22, EN55011

Frequently asked questions

What communication protocols does the Acuvim II support?

The Acuvim II supports Modbus RTU and BACnet MS/TP via RS485, and with optional modules adds Modbus TCP/IP, BACnet IP, IEC 61850, DNP 3.0, SNMP, HTTP/HTTPS, FTP, SMTP, MQTT, and PROFIBUS DP.

What is the accuracy class for active energy measurement?

Active energy meets IEC 62053-22 class 0.1s and ANSI C12.20 class 0.1 revenue-grade accuracy.

Which current transformer types are compatible with the Acuvim II?

The meter is directly compatible with 5A, 1A, 80mA, 100mA, 200mA, 333mV, and Rogowski coil current transformers.

What is the operating temperature range for the Acuvim II?

The operating temperature range is -25°C to 70°C (-13°F to 158°F).