Yaskawa Varispeed E7 CIMR-E7B Error OU: Main Circuit Overvoltage

Yaskawa Varispeed E7 CIMR-E7B inverter · taken from the manufacturer’s manual, pages cited

Error codeOU

Main Circuit Overvoltage occurs when deceleration time is too short, supply voltage is too high, or DC bus voltage exceeds the overvoltage detection threshold. The manual's first action is: “Extend deceleration time or connect a braking option component (brake resistor unit, brake unit).”

Model
Yaskawa Varispeed E7 CIMR-E7B
Display shows
Main Circuit Overvoltage (OU)
Type
Error code
Source
Manual p. 255

What OU means

Main Circuit Overvoltage p. 255

Common causes

  • Deceleration time is too short, causing excessive regenerative energy from the motor. p. 255
  • Supply voltage is too high. p. 255
  • Main circuit overvoltage: DC bus voltage exceeds the overvoltage detection threshold. Approximately 410 V for 200 V class, approximately 820 V for 400 V class. p. 255

What to do

  1. Extend deceleration time or connect a braking option component (brake resistor unit, brake unit). p. 255
  2. Reduce the voltage within the power supply’s specified range. p. 255
  3. Supply voltage is too high. Reduce the voltage within the power supply’s specified range. p. 255

Before you service the product, read the safety instructions in the manual p. 4.

If OU is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Yaskawa service.

This page summarises what the manufacturer’s manual says about OU; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Yaskawa. Found a mistake? Report an error.