Internal fault occurs when 10V voltage is too low, and control card terminal 50 voltage is below 10 V, requiring removal of some loads because the 10 V power supply is overloaded with maximum current 15 mA or minimum resistance 590 ohms. The manual's first action is: “Control card terminal 50 voltage is below 10 V. Please remove some loads on terminal 50 because the 10 V power supply is overloaded. Maximum current is 15 mA, or minimum resistance is 590 ohms.”
- Model
- VLT HVAC Drive
- Display shows
- Internal fault (131072)
- Type
- Fault code
- Source
- Manual p. 73
What 131072 means
Internal fault p. 73
Common causes
- 10V voltage too low p. 73
What to do
- Control card terminal 50 voltage is below 10 V. Please remove some loads on terminal 50 because the 10 V power supply is overloaded. Maximum current is 15 mA, or minimum resistance is 590 ohms. p. 73
Before you service the product, read the safety instructions in the manual p. 75.
If 131072 is still not resolved
This page summarises what the manufacturer’s manual says about 131072; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with VLT. Found a mistake? Report an error.