One or more analogue input signals are below 50% of the minimum signal range due to a defective cable, loose connection, or malfunctioning source. The manual's first action is: “Replace the defective parts. Do a check of the analogue input circuit. Make sure that parameter AI1 Signal Range is set correctly.”
- Model
- Vacon 100 Flow
- Display shows
- AI low fault (50)
- Type
- Fault code
- Source
- Manual p. 375
What 50 means
AI low fault p. 375
Common causes
- 1 or more of the available analogue input signals is below 50% of the minimum signal range. A control cable is defective or loose. A malfunction in a signal source. p. 375
What to do
- Replace the defective parts. Do a check of the analogue input circuit. Make sure that parameter AI1 Signal Range is set correctly. p. 375
Before you service the product, read the safety instructions in the manual p. 88.