Fault code41
The IGBT temperature is too high due to excessive motor load, high ambient temperature, or incorrect parameter settings. The manual's first action is: “Do a check of the parameter settings.”
- Model
- Vacon 100 Flow
- Display shows
- IGBT temperature (41)
- Type
- Fault code
- Source
- Manual p. 374
What 41 means
IGBT temperature p. 374
Common causes
- The calculated IGBT temperature is too high. p. 374
- the motor load is too high p. 374
- the ambient temperature is too high p. 374
- hardware malfunction p. 374
What to do
- Do a check of the parameter settings. p. 374
- Examine the actual quantity and flow of cooling air. p. 374
- Do a check of the ambient temperature. p. 374
- Examine the heatsink for dust. Make sure that the switching frequency is not too high in relation to the ambient temperature and the motor load. p. 374