Toshiba VF-AS1 Error OC1P: Overcurrent flowing in element during acceleration (Overheat)

Toshiba VF-AS1 inverter · taken from the manufacturer’s manual, pages cited

Error codeOC1P

Overcurrent flowing in element during acceleration (Overheat) is caused by too short acceleration time RLC, improper Vf setting, or restart signal input to rotating motor after momentary stop. The manual's first action is: “37”

Model
Toshiba VF-AS1
Display shows
OC1P
Type
Error code
Source
Manual p. 216

What OC1P means

Overcurrent flowing in element during acceleration (Overheat) p. 216

Common causes

  • The acceleration time RLC is too short. p. 216
  • The Vf setting is improper. p. 216
  • A restart signal is input to the rotating motor after a momentary stop, etc. p. 216
  • A special motor (e.g. motor with a small impedance) is used. p. 216
  • Manual brake boost value (ub) is large. p. 216
  • Decrease FBG (stall prevention level) to 130 as a guide. p. 216
  • Increase CF (carrier frequency) setting value if it is set at lower value (2kHz or less). p. 216

What to do

  1. 37 p. 216
  2. Increase the acceleration time RLC. p. 216
  3. Check the Vf parameter setting. p. 216
  4. Use U5 (Auto-restart) and U6 (Regenerative power ride-through control). p. 216
  5. Increase the carrier frequency F. p. 216
  6. Decrease ub setting value. p. 216

Before you service the product, read the safety instructions in the manual p. 17.

If OC1P is still not resolved

  • Read the Instruction Manual p. 17
    “Read the Instruction Manual.”

This page summarises what the manufacturer’s manual says about OC1P; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Toshiba. Found a mistake? Report an error.