TECO A510 Error FU: Fuse Open

TECO A510 inverter · taken from the manufacturer’s manual, pages cited

Error codeFU

FU on the TECO A510 is listed in the manual as: Fuse Open. The manual's first action is: “Check whether the motor and cables are shorted or have insulation damage. Repair/replace the inverter.”

Model
TECO A510
Display shows
Fuse Open (FU)
Type
Error code
Source
Manual p. 251

What FU means

Fuse Open p. 251

Common causes

  • Output side short circuit of the inverter has damaged the power semiconductor. p. 251
  • DC fuse (Models 230 V 50 HP and above, 460 V 75 HP and above) is open. p. 251

What to do

  1. Check whether the motor and cables are shorted or have insulation damage. Repair/replace the inverter. p. 251
  2. Check for a short circuit between terminal e and U/T1, V/T2, W/T3. p. 251

Before you service the product, read the safety instructions in the manual p. 252.

If FU is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact TECO service.