Drive belt fault detected means load condition indicates a drive‑belt fault or a mechanical fault. The manual's first action is: “Check the following: 1. Whether the drive chain is broken, seized, or blocked. 2. Whether any external speed sensor (if used) is operating correctly; verify that the values of the following parameters are correct: P0409 (pulses per minute at rated speed), P2191 (frequency deviation for drive‑belt fault), P2192 (delay time corresponding to the allowed deviation). 3. If torque control is used, ensure the following parameters are correct: P2182 (frequency threshold f1), P2183 (frequency threshold f2), P2184 (frequency threshold f3), P2185 (torque upper limit 1), P2186 (torque lower limit 1), P2187 (torque upper limit 2), P2188 (torque lower limit 2), P2189 (torque upper limit 3), P2190 (torque lower limit 3), P2192 (delay time corresponding to the allowed deviation). 4. Add lubrication if required.”
- Model
- Siemens MICROMASTER 440
- Display shows
- Drive belt fault detected (F0452)
- Type
- Fault code
- Source
- Manual p. 99
What F0452 means
Drive belt fault detected p. 99
Common causes
- Load condition indicates a drive‑belt fault or a mechanical fault. p. 99
What to do
- Check the following: 1. Whether the drive chain is broken, seized, or blocked. 2. Whether any external speed sensor (if used) is operating correctly; verify that the values of the following parameters are correct: P0409 (pulses per minute at rated speed), P2191 (frequency deviation for drive‑belt fault), P2192 (delay time corresponding to the allowed deviation). 3. If torque control is used, ensure the following parameters are correct: P2182 (frequency threshold f1), P2183 (frequency threshold f2), P2184 (frequency threshold f3), P2185 (torque upper limit 1), P2186 (torque lower limit 1), P2187 (torque upper limit 2), P2188 (torque lower limit 2), P2189 (torque upper limit 3), P2190 (torque lower limit 3), P2192 (delay time corresponding to the allowed deviation). 4. Add lubrication if required. p. 99
Before you service the product, read the safety instructions in the manual p. 7.
If F0452 is still not resolved
This page summarises what the manufacturer’s manual says about F0452; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.