The Motor Parameter Auto-Detection Fault occurs when there is a motor parameter auto-detection fault with alarm values indicating load disappeared, current limit reached during auto-detection, or detected stator resistance less than 0.1% or great. The manual's first action is: “0: Verify that the motor is correctly connected to the inverter. 1‑40: Check that motor parameters P304‑P311 are correct. Verify the motor wiring configuration (star or delta).”
- Model
- Siemens MICROMASTER 440
- Display shows
- Motor Parameter Auto‑Detection Fault (F0041)
- Type
- Alarm code
- Source
- Manual p. 97
What F0041 means
Motor Parameter Auto‑Detection Fault p. 97
Common causes
- Motor parameter auto‑detection fault. Alarm value =0: Load disappeared. Alarm value =1: Current limit reached during auto‑detection. Alarm value =2: Detected stator resistance less than 0.1 % or greater than 100 %. Alarm value =3: Detected rotor resistance less than 0.1 % or greater than 100 %. Alarm value =4: Detected stator reactance less than 50 % or greater than 500 %. Alarm value =5: Detected supply reactance less than 50 % or greater than 500 %. Alarm value =6: Detected rotor time constant less than 10 ms or greater than 5 s. Alarm value =7: Detected total leakage reactance less than 5 % or greater than 50 %. Alarm value =8: Detected stator leakage reactance less than 25 % or greater than 250 %. Alarm value =9: Detected rotor leakage inductance less than 25 % or greater than 250 %. Alarm value =20: Detected IGBT on‑state voltage less than 0.5 V or greater than 10 V. Alarm value =30: Current controller reached voltage limit. Alarm value =40: Detected data set is internally inconsistent; at least one auto‑detection datum is erroneous. Based on reactance Zb percentage = Vmot,nom / sqrt(3) / Imot,nom p. 97
What to do
- 0: Verify that the motor is correctly connected to the inverter. 1‑40: Check that motor parameters P304‑P311 are correct. Verify the motor wiring configuration (star or delta). p. 97
Before you service the product, read the safety instructions in the manual p. 7.
If F0041 is still not resolved
This page summarises what the manufacturer’s manual says about F0041; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.