Motor I²T over‑temperature means motor overload with too long work time in the load’s “work‑stop” cycle. The manual's first action is: “Regardless of the type of over‑temperature, check the following: 1. Motor temperature alarm limit (P0604). 2. Motor operating ambient temperature (P0625). 3. If P0601 = 0 or 1, verify: • That the name‑plate data are correct (if not performing fast tuning). • When automatic motor parameter detection is performed (P1910 = 0), the equivalent circuit data are accurate. • That the motor weight (P0344) is reliable; modify if necessary. • If the motor is not a Siemens standard motor, adjust the over‑temperature reference values via parameters P0626, P0627, and P0628. 4. If P0601 = 1, verify: • That the temperature value shown by r0035 is reliable. • That the sensor is a KTY 84 (other sensors are not supported).”
- Model
- Siemens MICROMASTER 440
- Display shows
- Motor I²T over‑temperature (A0511)
- Type
- Alarm code
- Source
- Manual p. 100
What A0511 means
Motor I²T over‑temperature p. 100
Common causes
- Motor overload. In the load’s “work‑stop” cycle, the work time is too long. p. 100
What to do
- Regardless of the type of over‑temperature, check the following: 1. Motor temperature alarm limit (P0604). 2. Motor operating ambient temperature (P0625). 3. If P0601 = 0 or 1, verify: • That the name‑plate data are correct (if not performing fast tuning). • When automatic motor parameter detection is performed (P1910 = 0), the equivalent circuit data are accurate. • That the motor weight (P0344) is reliable; modify if necessary. • If the motor is not a Siemens standard motor, adjust the over‑temperature reference values via parameters P0626, P0627, and P0628. 4. If P0601 = 1, verify: • That the temperature value shown by r0035 is reliable. • That the sensor is a KTY 84 (other sensors are not supported). p. 100
Before you service the product, read the safety instructions in the manual p. 7.
If A0511 is still not resolved
This page summarises what the manufacturer’s manual says about A0511; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.