Siemens MICROMASTER 440 Error A0511: Motor I²T over‑temperature

Siemens MICROMASTER 440 variable frequency drive · taken from the manufacturer’s manual, pages cited

Alarm codeA0511

Motor I²T over‑temperature means motor overload with too long work time in the load’s “work‑stop” cycle. The manual's first action is: “Regardless of the type of over‑temperature, check the following: 1. Motor temperature alarm limit (P0604). 2. Motor operating ambient temperature (P0625). 3. If P0601 = 0 or 1, verify: • That the name‑plate data are correct (if not performing fast tuning). • When automatic motor parameter detection is performed (P1910 = 0), the equivalent circuit data are accurate. • That the motor weight (P0344) is reliable; modify if necessary. • If the motor is not a Siemens standard motor, adjust the over‑temperature reference values via parameters P0626, P0627, and P0628. 4. If P0601 = 1, verify: • That the temperature value shown by r0035 is reliable. • That the sensor is a KTY 84 (other sensors are not supported).”

Model
Siemens MICROMASTER 440
Display shows
Motor I²T over‑temperature (A0511)
Type
Alarm code
Source
Manual p. 100

What A0511 means

Motor I²T over‑temperature p. 100

Common causes

  • Motor overload. In the load’s “work‑stop” cycle, the work time is too long. p. 100

What to do

  1. Regardless of the type of over‑temperature, check the following: 1. Motor temperature alarm limit (P0604). 2. Motor operating ambient temperature (P0625). 3. If P0601 = 0 or 1, verify: • That the name‑plate data are correct (if not performing fast tuning). • When automatic motor parameter detection is performed (P1910 = 0), the equivalent circuit data are accurate. • That the motor weight (P0344) is reliable; modify if necessary. • If the motor is not a Siemens standard motor, adjust the over‑temperature reference values via parameters P0626, P0627, and P0628. 4. If P0601 = 1, verify: • That the temperature value shown by r0035 is reliable. • That the sensor is a KTY 84 (other sensors are not supported). p. 100

Before you service the product, read the safety instructions in the manual p. 7.

If A0511 is still not resolved

  • contact the dealer or service center p. 6
    “如果不遵守有关要求 不采取相应 措施 就会造成死亡或严重的人身伤害”
  • contact the dealer or service center p. 7
    “请仔细阅读这些“警告”,“注意”和“提示””

This page summarises what the manufacturer’s manual says about A0511; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.