DC circuit maximum voltage Vdc-max controller not active occurs when the DC circuit voltage cannot be kept within the specified range or the supply voltage is too high or the motor operates in regenerative braking mode. The manual's first action is: “Check the following: 1. Input supply voltage (P0210) must be within the allowed range. 2. The load must be matched.”
- Model
- Siemens MICROMASTER 430
- Display shows
- DC circuit maximum voltage Vdc-max controller not active (A0910)
- Type
- Alarm code
- Source
- Manual p. 90
What A0910 means
DC circuit maximum voltage Vdc-max controller not active p. 90
Common causes
- The DC circuit maximum voltage Vdc-max controller is not active because it cannot keep the DC circuit voltage (r0028) within the range specified by (P2172). p. 90
- If the supply voltage (P0210) remains too high, this alarm may occur. p. 90
- If the motor is driven by the load, causing it to operate in regenerative braking mode, this alarm may occur. p. 90
- During a downhill ramp, if the load inertia is especially large, this alarm may occur. p. 90
What to do
- Check the following: 1. Input supply voltage (P0210) must be within the allowed range. 2. The load must be matched. p. 90
Before you service the product, read the safety instructions in the manual p. 7.
If A0910 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Siemens service.
This page summarises what the manufacturer’s manual says about A0910; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.