Error codeLOE

LOE indicates a measurement difficulty occurring for longer than the Failsafe Timer setting or a false echo lock condition. The manual's first action is: “LOE is flashed alternately with the Reading display. Under certain conditions, a measurement difficulty may cause the SITRANS LU 01 to lock on to a false echo and report a fixed or wrong reading.”

Model
Siemens LU 01
Display shows
LOE
Type
Error code
Source
Manual p. 104

What LOE means

If a measurement difficulty occurs for greater than the Failsafe Timer (P070) setting p. 104

Common causes

  • If a measurement difficulty occurs for greater than the Failsafe Timer (P070) setting p. 104
  • If LOE is displayed p. 104
  • For optimum performance p. 104
  • To display Echo Confidence in the RUN mode: p. 104
  • To display Echo Confidence in PROGRAM mode p. 104
  • To update the value displayed after each aiming adjustment... p. 104

What to do

  1. LOE is flashed alternately with the Reading display. Under certain conditions, a measurement difficulty may cause the SITRANS LU 01 to lock on to a false echo and report a fixed or wrong reading. p. 104
  2. ensure that the: 1. Material (object) surface monitored is within the maximum range of the transducer. 2. Transducer (P004) value matches the transducer used. 3. Transducer is located and aimed properly. (See the Transducer manual for maximum range, mounting and rough aiming instructions.) p. 104
  3. adjust the transducer aiming while monitoring the Echo Confidence (P805) for various material levels over the measurement range. When complete, set the transducer aiming at the best angle for all levels. p. 104
  4. Press and hold for 4 seconds (Failsafe Time Left changes to the Short : Long Confidence display). p. 104
  5. access the Echo Confidence (P805) parameter. p. 104
  6. Press (5 times or more to verify stability) p. 104

Before you service the product, read the safety instructions in the manual p. 32.

If LOE is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Siemens service.

This page summarises what the manufacturer’s manual says about LOE; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.