Siemens 3RW34 Error LED1

Siemens 3RW34 soft starter · taken from the manufacturer’s manual, pages cited

Fault codeLED1

LED1 indicates phase loss, EEPROM failure, or no mains voltage. The manual's first action is: “Follow steps 3 and 4 described in Section 6.5 to check for the presence of normal three‑phase supply voltage.”

Model
Siemens 3RW34
Display shows
LED1
Type
Fault code
Source
Manual p. 37

What LED1 means

Phase loss p. 37

Common causes

  • Phase loss p. 37
  • EEPROM failure p. 37
  • No mains voltage p. 37
  • No control voltage p. 37
  • Motor not connected to the soft starter p. 37
  • Supply line circuit to the controller is open p. 37
  • Cable connection unreliable and control circuit board defective p. 37
  • Motor defect p. 37

What to do

  1. Follow steps 3 and 4 described in Section 6.5 to check for the presence of normal three‑phase supply voltage. p. 37
  2. Replace the control circuit board; replacement precautions are in the user manual supplied with the new board. Return the defective control circuit board to the manufacturer. p. 37
  3. Inspect the supply‑side terminals L1, L2 and L3 to see if the isolation switches are in the released position, whether the protective switch has tripped, and whether the connections at the terminals are reliable. Then, using steps 3, 4 and 6 of Section 6.5, verify that correct three‑phase supply voltage is present. p. 37
  4. Check the supply‑side control terminals X1 and X2, verify whether the fuse has blown, whether the circuit is open, and whether the terminal connections are reliable. Verify that the correct control voltage is present (control voltage range is 10% to 15% of the soft starter’s rated data). If the control circuit includes a control transformer (CPT), check that primary voltage is present and that the primary tap is appropriate. p. 37
  5. Check that all series isolation switches or isolation contacts are closed. p. 37
  6. Inspect terminals A1 and A2 for the presence of control voltage; if no voltage is present, verify that the wiring to terminals A1 and A2 is reliable, and that the related control terminals (e.g., 13, 14, etc.) are properly connected to the control circuit’s actuators (such as start‑stop devices, isolation contacts). p. 37
  7. Disconnect the control voltage and check that the conductor connections between the control circuit board and the RC interference‑suppression components are reliable. If problems are found, disconnect the mains voltage and replace the control circuit board and/or the RC component, or request assistance from the manufacturer. p. 37
  8. Eliminate motor defects and faults according to the user manual provided by the motor manufacturer. p. 37

Before you service the product, read the safety instructions in the manual p. 15.

If LED1 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Siemens service.

This page summarises what the manufacturer’s manual says about LED1; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.