Schneider Electric ATV61 Error PHF: [Input Phase Loss]

Schneider Electric ATV61 · taken from the manufacturer’s manual, pages cited

Fault codePHF

PHF means there is an input phase loss, possibly due to incorrect power supply, blown fuse, single-phase fault, or three-phase ATV61 powered by single-phase main supply. The manual's first action is: “Check power connections and fuse.”

Model
Schneider Electric ATV61
Display shows
[Input Phase Loss] (PHF)
Type
Fault code
Source
Manual p. 244

What PHF means

[Input Phase Loss] p. 244

Common causes

  • Incorrect inverter power supply or fuse blown. p. 244
  • Single-phase fault. p. 244
  • Three-phase ATV61 powered by single-phase main supply. p. 244
  • Load imbalance. p. 244
  • This protection is only effective when the inverter is unloaded. p. 244

What to do

  1. Check power connections and fuse. p. 244
  2. Use a three-phase main supply. p. 244
  3. Disable the fault by setting [Input Phase Loss] (IPL) = [No] (No) (see page 194). p. 244

Before you service the product, read the safety instructions in the manual p. 54.

If PHF is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Schneider Electric service.

This page summarises what the manufacturer’s manual says about PHF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.