Overcurrent indicates a short-circuit on the starter output, internal short-circuit, bypass contactor stuck, or overrate starter. The manual's first action is: “Switch the starter off. • Check the connecting cables and the motor isolation • Check the thyristors • Check the bypass contactor (contact stuck) • Check the parameter value bSt in the menu drC page 139”
- Model
- Schneider Electric ATS48
- Display shows
- OEF
- Type
- Fault code
- Source
- Manual p. 159
What OEF means
Overcurrent: • impeding short-circuit on starter output • internal short-circuit • bypass contactor stuck • overrate starter p. 159
Common causes
- Overcurrent: • impeding short-circuit on starter output • internal short-circuit • bypass contactor stuck • overrate starter p. 159
What to do
- Switch the starter off. • Check the connecting cables and the motor isolation • Check the thyristors • Check the bypass contactor (contact stuck) • Check the parameter value bSt in the menu drC page 139 p. 159
Before you service the product, read the safety instructions in the manual p. 146.
If OEF is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Schneider Electric service.
This page summarises what the manufacturer’s manual says about OEF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.