Schneider Electric ATS48 Error BHF: Starter thermal fault

ATS48 soft starter · taken from the manufacturer’s manual, pages cited

Fault codeBHF

Starter thermal fault means the starter has overheated. The manual's first action is: “Check the mechanism (wear, mechanical play, lubrication, blockages, etc.).”

Model
Schneider Electric ATS48
Display shows
Starter thermal fault (BHF)
Type
Fault code
Source
Manual p. 162

What BHF means

Starter thermal fault p. 162

What to do

  1. Check the mechanism (wear, mechanical play, lubrication, blockages, etc.). p. 162
  2. Check the sizing of the starter in relation to the motor and the mechanical requirement. p. 162
  3. Check the operation of the fan (if the ATS48 used has one), ensuring that the air passage is not obstructed in any way and the heatsink is clean. Ensure that the mounting recommendations are observed. p. 162
  4. Wait for the ATS48 to cool before restarting. p. 162

Before you service the product, read the safety instructions in the manual p. 146.

If BHF is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Schneider Electric service.

This page summarises what the manufacturer’s manual says about BHF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.