Schneider Electric Altivar 71W/E5 Error PHF: [INPUT PHASE LOSS]

Schneider Electric Altivar 71W/E5 · taken from the manufacturer’s manual, pages cited

Fault codePHF

The drive has detected a loss of input phase, possibly due to incorrect power supply, blown fuse, or unbalanced load. The manual's first action is: “Check the power connection and the fuses Reset Use a 3-phase line Disable the fault by setting [Input phase loss] (IPL) = [Ne] (nC) (consult the CD-ROM supplied with the drive).”

Model
Schneider Electric Altivar 71W/E5
Display shows
[INPUT PHASE LOSS] (PHF)
Type
Fault code
Source
Manual p. 79

What PHF means

[INPUT PHASE LOSS] p. 79

Common causes

  • Drive incorrectly supplied or a fuse blown Failure of one phase 3-phase ATV71 used on a single phase line supply Unbalanced load This protection only operates with the drive on load p. 79

What to do

  1. Check the power connection and the fuses Reset Use a 3-phase line Disable the fault by setting [Input phase loss] (IPL) = [Ne] (nC) (consult the CD-ROM supplied with the drive). p. 79

Before you service the product, read the safety instructions in the manual p. 43.

If PHF is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Schneider Electric service.

This page summarises what the manufacturer’s manual says about PHF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.