The drive is not receiving proper power due to incorrect supply, blown fuses, or a missing phase. The manual's first action is: “Check the power connection and the fuses.”
- Model
- Schneider Electric Altivar 71
- Display shows
- [Input phase loss] (PHF)
- Type
- Fault code
- Source
- Manual p. 292
What PHF means
[Input phase loss] p. 292
Common causes
- Drive incorrectly supplied or a fuse blown p. 292
- Failure of one phase p. 292
- 3-phase ATV71 used on a single-phase line supply p. 292
What to do
- Check the power connection and the fuses. p. 292
- Use a 3-phase line supply. p. 292
- Disable the fault by [Input phase loss] (IPL) = [No] (nO). (page 242) p. 292
Before you service the product, read the safety instructions in the manual p. 16.
If PHF is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Schneider Electric service.
This page summarises what the manufacturer’s manual says about PHF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.