PHF indicates input phase loss, which may be caused by the drive being incorrectly powered or a fuse blown, failure of one phase, or a three-phase ATV61 used on a single-phase line supply. The manual's first action is: “Check the power connection and the fuses.”
- Model
- Schneider Electric Altivar 61
- Display shows
- [Input phase loss] (PHF)
- Type
- Fault code
- Source
- Manual p. 57
What PHF means
[Input phase loss] p. 57
Common causes
- Drive incorrectly powered or a fuse blown p. 57
- Failure of one phase p. 57
- Three-phase ATV61 used on a single-phase line supply p. 57
- Unbalanced load This protection only operates with the drive on load p. 57
What to do
- Check the power connection and the fuses. p. 57
- Use a three-phase line supply. p. 57
- Disable the fault by setting [Input phase loss] (IPL) = [No] (nO). p. 57
Before you service the product, read the safety instructions in the manual p. 33.
If PHF is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Schneider Electric service.
This page summarises what the manufacturer’s manual says about PHF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.