Communication fault between option card and drive The manual's first action is: “Check the environment (electromagnetic compatibility). Check the connections. Check that no more than two option cards (max. permitted) have been installed on the drive. Replace the option card. Inspect/repair the drive.”
- Model
- Schneider Electric Altivar 61
- Display shows
- [Internal com. link] (ILF)
- Type
- Fault code
- Source
- Manual p. 53
What ILF means
[Internal com. link] p. 53
Common causes
- Communication fault between option card and drive p. 53
What to do
- Check the environment (electromagnetic compatibility). Check the connections. Check that no more than two option cards (max. permitted) have been installed on the drive. Replace the option card. Inspect/repair the drive. p. 53
Before you service the product, read the safety instructions in the manual p. 33.
If ILF is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Schneider Electric service.
This page summarises what the manufacturer’s manual says about ILF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.