Fault codeOL1
Drive overload means the drive is overloaded, the acceleration time is too short, or the DC injection current level is too high. The manual's first action is: “about 30 seconds after the occurrence of the fault”
- Model
- Schneider Electric Altivar 21
- Display shows
- drive overload (OL1)
- Type
- Fault code
- Source
- Manual p. 33
What OL1 means
drive overload p. 33
Common causes
- drive overload p. 33
- The acceleration time is too short. p. 33
- The DC injection current level is too high. p. 33
- The setting of parameter PL is incorrect. p. 33
- The drive is starting into a rotating load. p. 33
- The load is too large. p. 33
What to do
- about 30 seconds after the occurrence of the fault p. 33
- Increase the acceleration time parameters (ACC or FSOO). p. 33
- Reduce the setting of parameters F2S1 and/or F2S2. p. 33
- Select the correct setting for parameter PL. p. 33
- Enable catch on the fly, parameter F301. p. 33
- Set parameter F302 to 2. p. 33
- Use a drive with a higher power rating. p. 33
Before you service the product, read the safety instructions in the manual p. 5.
If OL1 is still not resolved
This page summarises what the manufacturer’s manual says about OL1; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.