Fault codeEF2
Ground fault means there is a ground fault in the motor or motor cables. The manual's first action is: “Using a 1000 V megger, check the motor and motor cables for ground faults.”
- Model
- Schneider Electric Altivar 21
- Display shows
- Ground fault (EF2)
- Type
- Fault code
- Source
- Manual p. 118
What EF2 means
Ground fault p. 118
Common causes
- Ground fault in motor or motor cables p. 118
What to do
- Using a 1000 V megger, check the motor and motor cables for ground faults. p. 118
Before you service the product, read the safety instructions in the manual p. 5.
If EF2 is still not resolved
This page summarises what the manufacturer’s manual says about EF2; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.