Schneider Altivar 71 Error PHF: [INPUT PHASE LOSS]

Schneider Altivar 71 · taken from the manufacturer’s manual, pages cited

Fault codePHF

The PHF code indicates an input phase loss caused by the drive being incorrectly supplied, a blown fuse, failure of one phase, a three-phase ATV71 used on a single-phase line supply, or an unbalanced load. The manual's first action is: “Check the power connection and the fuses. Reset Use a three-phase line supply. Disable the fault by setting [Input phase loss] (IPL) = [No] (nO). (page 65)”

Model
Schneider Altivar 71
Display shows
[INPUT PHASE LOSS] (PHF)
Type
Fault code
Source
Manual p. 71

What PHF means

[INPUT PHASE LOSS] p. 71

Common causes

  • Drive incorrectly supplied or a fuse blown Failure of one phase Three-phase ATV71 used on a single-phase line supply Unbalanced load This protection only operates with the drive on load. p. 71

What to do

  1. Check the power connection and the fuses. Reset Use a three-phase line supply. Disable the fault by setting [Input phase loss] (IPL) = [No] (nO). (page 65) p. 71

Before you service the product, read the safety instructions in the manual p. 40.

If PHF is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Schneider service.

This page summarises what the manufacturer’s manual says about PHF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider. Found a mistake? Report an error.