The motor is not connected, motor power is too low, the output contactor is open, or there is instability in the motor current. The manual's first action is: “• Check the connections from the drive to the motor. • If an output contactor is being used, consult the CD-ROM supplied with the drive. • Test on a low power motor or without a motor: In factory settings mode, motor output phase loss detection is active [Output Phase Loss] (CPL) = [Yes] (YES). To check the drive in a test or maintenance environment, without having to use a motor with the same rating as the drive (in particular for high-power drives), deactivate motor phase loss detection [Output Phase Loss] (OPL) = [No] (nO) (consult the CD-ROM supplied with the drive). • Check and optimize the [Rated motor volt.] (UnS) and [Rated mot. current] (nCr) parameters and perform an [Auto tuning] (tUn) operation.”
- Model
- Schneider Altivar 71
- Display shows
- [3 MOTOR PHASE LOSS] (OPF2)
- Type
- Fault code
- Source
- Manual p. 70
What OPF2 means
[3 MOTOR PHASE LOSS] p. 70
Common causes
- • Motor not connected or motor power too low • Output contactor open • Instantaneous instability in the motor current p. 70
What to do
- • Check the connections from the drive to the motor. • If an output contactor is being used, consult the CD-ROM supplied with the drive. • Test on a low power motor or without a motor: In factory settings mode, motor output phase loss detection is active [Output Phase Loss] (CPL) = [Yes] (YES). To check the drive in a test or maintenance environment, without having to use a motor with the same rating as the drive (in particular for high-power drives), deactivate motor phase loss detection [Output Phase Loss] (OPL) = [No] (nO) (consult the CD-ROM supplied with the drive). • Check and optimize the [Rated motor volt.] (UnS) and [Rated mot. current] (nCr) parameters and perform an [Auto tuning] (tUn) operation. p. 70
Before you service the product, read the safety instructions in the manual p. 40.
If OPF2 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Schneider service.
This page summarises what the manufacturer’s manual says about OPF2; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider. Found a mistake? Report an error.