Schneider Altivar 71 Error EnF: [ENCODER FAULT]

Schneider Altivar 71 · taken from the manufacturer’s manual, pages cited

Fault codeEnF

Encoder fault means the encoder feedback is faulty. The manual's first action is: “Check [Number of pulses] (PGI) and [Encoder type] (En3) (consult the CD-ROM supplied with the drive).\nCheck that the encoder's mechanical and electrical operation, its power supply and connections are all correct.\nCheck and, if necessary, reverse the direction of rotation of the motor ([Output Ph rotation] (PHr) parameter on page 66) or the encoder signals.”

Model
Schneider Altivar 71
Display shows
[ENCODER FAULT] (EnF)
Type
Fault code
Source
Manual p. 67

What EnF means

[ENCODER FAULT] p. 67

Common causes

  • Encoder feedback fault p. 67

What to do

  1. Check [Number of pulses] (PGI) and [Encoder type] (En3) (consult the CD-ROM supplied with the drive).\nCheck that the encoder's mechanical and electrical operation, its power supply and connections are all correct.\nCheck and, if necessary, reverse the direction of rotation of the motor ([Output Ph rotation] (PHr) parameter on page 66) or the encoder signals. p. 67

Before you service the product, read the safety instructions in the manual p. 40.

If EnF is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Schneider service.

This page summarises what the manufacturer’s manual says about EnF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider. Found a mistake? Report an error.